BluePoint Energy Cogeneration Modules - Gaseous

Source |
Engine |
G3406 NA |
G3406 TA |
G3408 TA |
G3412 NA |
G3412 TA |
G3412C LE |
|---|---|---|---|---|---|---|---|
| Energy Input1 |
Btu/hour - LHV |
1,618,000 | 2,191,200 | 2,682,000 | 2,786,820 | 4,064,599 | 4,731,120 |
| Therms per Hour - HHV3 |
18.0 | 24.3 | 29.8 | 31.0 | 45.2 | 52.6 | |
| Electrical Output2 |
kWe @ 1.0 pf | 153 | 211 | 257 | 250 | 385 | 456 |
| Electrical Efficiency |
32.3% | 32.8% | 32.7% | 30.6% | 32.3% | 32.9% | |
| Thermal Output1 |
Output - Therms/hour |
9.5 | 11.6 | 14.6 | 15.7 | 22.2 | 21.3 |
| Total Thermal Efficiency |
58.4% | 53.1% | 54.3% | 56.4% | 54.7% | 45.0% | |
| Overall Efficiency | 90.7% | 85.9% | 87.0% | 87.0% | 87.1% | 78.0% | |
| Thermal Production: | Data is based on the production of hot water for domestic use at approximately 160°F and the use of an interposing heat exchanger for prime mover isolation. BPE products are capable of serving a wide range of thermal load requirements however overall module efficiency may be impacted by application specific requirements. |
|---|---|
| Emissions & Regulatory Compliance: |
BluePoint Energy utilizes emission strategies specific to a wide variety of jurisdictional and regulatory parameters. Please contact a BluePoint representative for information on how we can address your unique requirements. |
| 1) Thermal output and energy input based on engine manufacturer's published data and exhaust cooled to 250°F 2) Electrical output based on engine and generator manufacturer's published data 3) HHV calculated as: LHV ÷ 0.9 = HHV (source: AGA) 4) Emissions after NSCR |
Caterpillar holds the following tolerances for published information: | |
| Power: | +/- 3% | |
| Fuel Rate: | +/- 5% | |
| Exhaust Temperature: | +/- 8% | |
| JW Heat Rejection: | +/- 10% | |
| Exhaust Heat Rejection: | +/- 10% | |
| Ambient Radiation: | +/- 50% | |